10.5KV 3MW Dummy Load Bank 3 Phase AC Variable For Generator Testing

Hebei Kaixiang Electrical Technology Co., Ltd
Contact Now

10.5KV 3MW Dummy Load Bank 3 Phase AC Variable For Generator Testing

  • 1
  • 2

Brand Name : KAIXIANG

Model Number : 3000KW

Certification : ISO9001

Place of Origin : HEBEI CHINA

MOQ : ONE SET

Price : negotiable

Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram,

Supply Ability : 10 SET ONE MONTH

Delivery Time : ONE MONTH AFTER GET DEPOSIT

Packaging Details : WOODEN CASE

Resistive Load : 3000 kW

Power Factor : 1

Load Tolerance (each step) : ±5%

Load Tolerance (overall) : ±3%

Fan &Control Voltage : External AC 3 phase 4 line, 380V/50Hz

Communication Interface : RS485,RS232

Insulation : F

Max Protection Grade : IP54

Contact Now

10.5KV 3MW Dummy Load Bank 3 Phase AC Variable For Generator Testing

Product Description

The system can be used with a computer to realize the intelligent control, automatically completing the special test to all electrical parameters of generating set and generating tables, graphs, and supporting the print, comprehensively from the cumbersome manual operation to provide scientific and efficient detection means for the power generating sets.

Technical Parameters

Rating voltage/frequency 10.5kV, 3 phase 50Hz
Max Load Power Resistive Load: 3000kW
Load Resolution Resistive Load: 6steps, 100kW,200kW,300kW,700kW,800kW,900kW
Power Factor 1
Load Tolerance ±5%
Load Tolerance (overall) ±3%
Fan &Control Voltage External AC 3 phase 4 line, 380V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)
Control power input——Connector-bar

Communication Interface RS485,RS232
Insulation F
Max Protection Grade IP54
Duty Cycle Continuous
Cooling Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
Enclosure Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal Lighting Adequate internal lighting will be provided
Transportation Hoisting, there are lifting lug in top of casing
Color Grey RAL7035 or as required
Dimensions About 6058mm*2438mm*2591mm(L*W*H)
Ambient Temperature -10℃~+50℃
Relative Humidity ≤95%
Atmospheric Pressure 86~106kPa
Contactor Xiguang
Fuse Chuantai
Alloy Resistor (self-developing)
Data Processing Software (self-developing)


Technology Advantages

System can work with PC software to realize intelligent operation, automatically finish the parameters testing, and create testing data table, curves and reports that can be printed, reduce a lot of manual operation.

Application

Load Banks are used with Engine Generators, Battery Systems, UPS Systems, Inverters, Ground Power Units, Auxiliary Power Units, Aircraft Power Generators, Wind Generators, and Hydro Generators.


10.5KV 3MW Dummy Load Bank 3 Phase AC Variable For Generator Testing


Product Tags:

variable resistive load bank

      

portable load banks for generators

      
Best 10.5KV 3MW Dummy Load Bank 3 Phase AC Variable For Generator Testing wholesale

10.5KV 3MW Dummy Load Bank 3 Phase AC Variable For Generator Testing Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Hebei Kaixiang Electrical Technology Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)